Form I-RA/D 140/235 (Version A), Page 18
Heating
Thermostat
Pump Power
Installation
Pump Power
To connect the electrical power from the heater to the pump,
Use a 3 conductor, 14 gauge wire system - two 115 volt conductors
and a ground. Use BX if permitted, but make certain to follow
local codes for running conduit.
Refer to the wiring diagram for connecting terminals.
Heater Power Installation
DANGER: Make sure that the main circuit is OFF before making any wiring
connections. All wiring must be done in accordance with appropriate Codes!
Main Power
To install main power to the system (check the table below and the rating
plate on the furnace for current requirements),
Use #12 gauge stranded copper wire for RA and #8 gauge for RAD to
run a dedicated 115 volt, single phase, line from the power source to a
junction box mounted on the wall behind the heater or as required by
appropriate codes.
Run the length of appropriate conduit from the heater to the junction
box.
Connect the black wire to the hot lead.
Connect the white wire to the neutral lead.
Connect the green wire to the ground lead.
Install a fused manual reset, line voltage switch (field supplied) in this
main line
Electrical Ratings
A 24-volt thermostat is furnished as standard equipment.
DO NOT attempt to wire relays or other accessories to the thermostat con-
nections as these are not load terminals.
DO NOT install on or suspend the thermostat from the heater
DO NOT install thermostat on a cold outside wall
To install the thermostat,
Locate the thermostat five feet above the floor on an inside wall,
not in the path of warm or cold air currents nor in corners where air
may be pocketed
Remove the thermostat cover
Make sure the heat anticipator dial is set at 0.2 amps
Connect the wires through the back of the thermostat to the R & W
terminals
Set the ON/OFF switch on the heater electrical box to the “OFF”
position and connect the thermostat wires to the two “T” terminals
on the ignition controller.
Total Minimum Maximum
Current Circuit Fuse Size
Model Amperes Ampacity (Supply)
RA140 13 16 20
RAD140 24 30 40
RA235 14 18 20
RAD235 24 30 40