Reznor RA 140 Troubleshooting Guide Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
Form I-RA/D 140/235 (Version A), Mfg No. 110318 Rev 3, Page 11
Remote Fuel Pump
The Model OT-250 tank has a platform designed for attaching the remote
fuel pump.
Attach the fuel pump legs permanently either on the platform,
directly to a field-supplied tank, or in a location very near to the oil
tank.
Mount the remote pump assembly in an upright, horizontal position
as shown in the illustration.
NOTE: Do not mount the pump assembly in a vertical or
inverted position.
Pump
Supply Lines
Installation
CAUTION: Do not use TEFLON
®
based pipe dope or
TEFLON
®
tape to seal any pipe connections. (TEFLON
®
is a registered trademark of DuPont Chemical.) Use of
TEFLON
®
based pipe dope or TEFLON
®
tape will void
the pump warranty.
Nut, 3/8 tube size,
5/8-18 straight thread
- at the fuel inlet con-
nection on the heater
service tray
Relief
Valve
50 psi
Check
Valve
1/2 Pipe Plug
(for priming line)
Return Line to Tank
(1/8 NPT black iron pipe)
Vacuum Gauge
(install in upright position)
Hex Bushing
1/2 x x 3/4
90° Elbow , 1/2
End must
be open.
Suction Line
(Standard 1/2 pipe)
Foot Valve
Foot Valve
Strainer
Filter
Pump Inlet
Manifold
Pump
1/4 NPT
Connection
for Fuel Line
to Heater
Male Connection 3/8 Tube Size,
1/4 NPT, 5/8-18 Straight Thread;
Nut, 3/8 Tube Size, 5/8-18 Straight Thread
3/8 O.D. Copper
Tubing to Heater
Supply Lines
Read this section carefully before installing any supply lines. Since a suction line leak is nearly impossible to
find, take your time to assure all connections are leak-free during installation. Supply lines and fittings are
furnished by the installer. See the following illustration for minimum fittings required. Length of pipe and
tubing depends on the installation.
Run the suction line, using 1/2” standard black iron pipe, between the inlet
side of the filter and the foot valve. (Refer to the illustration.) A fuel line
filter with a cleanable strainer, a foot valve, a foot valve strainer, and a
vacuum gauge are provided with the heater. To prevent air from entering
the line, do not use union connections. Install the suction line components
Suction Line (portion
of supply line from
foot valve to pump)
Page view 10