C
CSA rating for altitudes to 2000 ft.
D
Size shown is for gas connection to a single stage gas valve, not supply line size.
E
Smaller or larger vent pipe diameters may be allowed; refer to the Venting Installation Manual, Form I-V-PV. If vent diameter is different from vent
connection, reducer/enlargers will be eld-required.
F
MOP = 2.25 x largest motor FLA + remaining load. Answer is rounded down to the next size of commercially available circuit breaker or fuse.
G
All other information in this table is based on a heater equipped with a standard 115 volt open fan motor.
Size 30 45 60 75 100 125 150 175 200 225 250 300 350 400
Input Heating Capacity
BTUH 30,000 45,000 60,000 75,000 105,000 120,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
kw/h 8.8 13.2 17.6 22.0 30.8 35.2 43.9 51.2 58.6 65.9 73.2 87.8 102.5 117.1
Thermal Efficiency (%) 82 83 83 83 83 83 83 83 83 83 83 83 83 83
Output Heating
Capacity
C
BTUH 24,600 37,350 49,800 62,250 87,150 99,600 124,500 145,250 166,000 186,750 207,500 249,000 290,500 332,000
kw/h 7.2 11.0 14.6 18.3 25.6 29.2 36.4 42.5 48.6 54.7 60.8 72.9 85.1 97.2
Gas Connection
(inches)
D
Natural 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Propane 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Vent Connection Size
E
(inches
diameter)
4 4 4 4 4 4 5 5 5 5 5 6 6 6
Control Amps (24 volt) 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Full Load Amps (115 volt) 1.9 2.4 2.4 3.3 3.9 5.1 3.8 3.8 4.6 7.5 7.5 11.0 11.0 11.0
Maximum Over Current Protection
(115V)
F
15 15 15 15 15 15 15 15 15 15 15 20
20 20
Normal Power Consumption
(watts)
109 155 155 217 276 354 392 392 491 747 747 1086 1086 1086
Discharge Air Temperature Rise
(°F)
50 55 60 60 60 60 60 60 60 60 60 60 60 60
Air Volume
CFM 456 629 769 961 1345 1537 1921 2242 2562 2882 3202 3843 4483 5123
M
3
/minute 12.9 17.8 21.8 27.5 36.7 45.9 54.4 63.5 72.5 81.6 90.7 108.8 126.9 145.1
Discharge Air Opening
Area
ft
2
0.96 0.96 1.25 1.25 2.01 2.01 2.56 2.56 2.56 3.51 3.51 4.79 4.79 4.79
M
2
0.09 0.09 0.12 0.12 0.19 0.19 0.24 0.24 0.24 0.33 0.33 0.45 0.45 0.45
Output Velocity
FPM 475 656 616 770 668 763 752 877 1003 820 911 802 936 1069
M/minute 145 200 188 238 196 245 229 267 306 250 278 244 285 326
Fan Motor HP
G
Open 0.02 0.03 0.03 0.06 1/30 1/20 1/6 1/6 1/6 1/4 1/4 1/2 1/2 1/2
Enclosed 0.06 0.06 0.06 0.06 1/20 1/20 1/4 1/4 1/4 1/4 1/4 1/2 1/2 1/2
Fan Motor RPM 1550 1550 1550 1550 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050
Fan Diameter (inches) 10 10 12 12 16 16 18 18 18 20 20 24 24 24
Sound Level
dba @
15 ft
40 40 40 49 54 55 51 52 53 56 56 59
61 62
Approximate Net
Weight
lbs 54 59 67 72 96 101 172 187 187 203 215 269 294 306
kg 24 27 30 33 44 46 78 85 85 92 98 122 133 139
Approximate Ship
Weight
lbs 61 66 74 79 118 123 204 219 219 245 257 321 346 358
kg 27 30 33 36 54 56 93 100 100 111 117 146 157 163
TECHNICAL DATA
Model UDAP
Vent cap
Thermostat
Thermostat guard with locking cover
Vertical louvers
Downturn nozzle kits
Gas conversion kits (natural and propane)
Primary/secondary controls for zoning up to six units
Ceiling suspension kit - Sizes 30-125
Hanger kits for 1” pipe
Stepdown transformer (for 208/115, 230/115 or 460/115 supply voltage)
Manual shutoff valves
OPTIONAL FEATURES -
FIELD INSTALLED
For installations where dirt, dust, and other air borne contamination is present in the indoor environment, it is
recommended to use separated combustion units (Model UDAS). These models use air from outside the space
for combustion. This will help reduce the build up of contaminates on the burner which would affect the combus-
tion process. Refer to the installation manuals for recommended frequency of maintenance and cleaning.
Form RZ-C-UH (Version H) Page 9